According to the topology of the substation and resistance measurements of down - leaders , the erosion diagnosis equation is built and the resistance variations of grounding grid branches are solved , and the erosion of grounding grid could be found through the fuzzy diagnosis regulation 利用接地網(wǎng)拓?fù)浣Y(jié)構(gòu)圖及接地網(wǎng)引下線間的電阻測(cè)量值,建立腐蝕診斷方程,通過求解診斷方程,計(jì)算出接地網(wǎng)支路電阻值變化量,采用模糊診斷方法判斷出接地網(wǎng)導(dǎo)體腐蝕的情況。
Big separated scales integrating with standing node when do elementary diagnosis is a good method to large - scale grounding grid . the number of the nodes for elementary diagnosis is ten percent of the total grid nodes number . and the erosible grid areas , important electrical equipments areas and the down - leaders areas should be considered enough 初步測(cè)量節(jié)點(diǎn)數(shù)的選擇以接地網(wǎng)節(jié)點(diǎn)總節(jié)點(diǎn)數(shù)的10 %為宜,另應(yīng)充分考慮接地網(wǎng)可能腐蝕的區(qū)域,重要電氣設(shè)備區(qū)域、接地引下線分布等情況。
The research shows that the protection of the industrial control system are not only need the external lightning protection system such as air terminals , down conductors and grounding system , but also need the internal lightning protection system such as equipotential bonding , shielding and surge protection of information system and electrical system 經(jīng)研究,對(duì)工業(yè)控制系統(tǒng)的防雷保護(hù)不僅要做好接閃器,引下線,接地體等基本的外部防護(hù),還要做好等電位聯(lián)結(jié),屏蔽,信號(hào)系統(tǒng)和電源系統(tǒng)的電涌保護(hù)等相關(guān)內(nèi)部防雷措施。